发电厂侧自动电压控制系统的原理及应用

刘铁成   

  1. 内蒙古华电包头发电有限公司,内蒙古包头014013
  • 收稿日期:1900-01-01 修回日期:1900-01-01 出版日期:2010-09-25 发布日期:2010-09-25

Principle and application of the automatic voltage control system in power plant side

LIU Tiecheng   

  1. Inner Mongolia Huadian Baotou Power Generation Corporation Limited, Baotou 014013, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2010-09-25 Published:2010-09-25

摘要: 发电厂侧自动电压控制系统(AVC)子站通过远动装置接收内蒙古调度中心自动电压控制系统(AVC)主站下发的电厂侧500kV母线指令。中控单元在充分考虑各种约束条件后,计算出对应的控制脉冲宽度,以通讯方式下发至自动电压控制系统(AVC)执行终端,由执行终端输出增减磁信号至分散控制系统(DCS),分散控制系统(DCS)给出指令至励磁系统,调节机组无功功率。发电机无功出力与机端电压受其励磁电流的影响,当励磁电流发生改变时,发电机的无功出力与机端电压也随之增减,并通过机端变压器进一步影响到母线电压的高低,励磁电流的增减可通过改变励磁调节器(AVR)给定值实现。

关键词: 自动电压控制系统(AVC), 分散控制系统(DCS), 励磁系统

Abstract: The AVC substation in power plant side receives the instruction of power plantside 500kV bus from the AVC main station of province dispatch center through the remote terminal unit. After considering various restraint conditions sufficiently, the center control unit calculates relevant width of the control pulse, and sends the calculation result to the executing terminal of the AVC system. The executing terminal output the increase or decrease excitation signal to the DCS. The DCS gives the instruction to the excitation system to regulate the reactive power of the generator set. The reactive power output and the terminal voltage of the generator are influenced by the excitation current. When the excitation current varies, the reactive power output and the terminal voltage of the generator will increase or decrease with the variation of the excitation current; and by the transformer beside the generator, the bus voltage will increase or decrease. The increase or decrease of the excitation current can be realized by adjusting the settings of the excitation regulator (AVR).

Key words: automatic voltage control (AVC) system, distributed control system (DCS), excitation system