华电技术 ›› 2015, Vol. 37 ›› Issue (11): 25-27.

• 研究与开发 • 上一篇    下一篇

应用等效电压源法计算6kV厂用母线短路电流

  

  1. 湖北华电襄阳发电有限公司,湖北 襄阳 441041
  • 出版日期:2015-11-25 发布日期:2016-01-26

The short circuit current calculation of 6 kV auxiliary bus using equivalent voltage source method

  1. Hubei Huadian Xiangyang Power Generation Company Limited,Xiangyang 441141,China
  • Online:2015-11-25 Published:2016-01-26

摘要:

摘要:结合某600MW机组高压厂用变压器出厂试验数据,以及6kV母线所接异步电动机参数,分别应用等效电压源法和传统方法, 计算6kV母线三相短路电流初始值,并对两种计算结果进行比较,计算中假定高压厂用变压器高压侧馈电网络阻抗为零。应用等效电压源法计算由厂用电源支路提供的短路电流,其平均值与采用传统方法的计算结果非常接近。

关键词: 关键词:600MW机组, 等效电压源法, 厂用母线, 短路电流计算

Abstract:

Abstract:Combining the factory experimental data of high voltage auxiliary transformer of a 600 MW unit and asynchronous motor parameters that 6 kV auxiliary bus connected,this paper calculated and compared the initial values of three phase short circuit current of the 6kV auxiliary bus using equivalent voltage source method and traditional method,respectively.In the calculations above,the feed network impedance on the high voltage side of high voltage auxiliary transformer is supposed to be 0.The calculations show that the average calculated values of short circuit current that provided by auxiliary power supply branch are very close to each other between equivalent voltage source method and traditional method.

Key words: ">Keywords:">600 ">MW unit, equivalent voltage source me thod, auxiliarybus, short circuit current calculation