Huadian Technology ›› 2015, Vol. 37 ›› Issue (11): 22-24.

Previous Articles     Next Articles

Comparing analysis on the application of positive low power protection and programmable reverse power protection in coal fired power unit

  

  1. Xian Thermal Power Research Institute Company Limited,Xian 710032,China
  • Online:2015-11-25 Published:2016-01-26

Abstract:

Abstract:This paper first introduced the principle,role and electrical process of programmable trip.And then it compared the differences of positive low power protection and reverse power protection for programmable trip on the aspects of logical configuration,role,trip mode and special working conditions such as load rejection.After that,it highlighted the differences of the two protection modes during load rejection
period and pointed out the feasibility and advantages of the application of positive low power protection in coal
fired power unit.At last,it proposed the setting principle of positive low power protection and verified its action logic combining with engineering example.