华电技术 ›› 2012, Vol. 34 ›› Issue (3): 78-81.
• 新能源 • 上一篇
冷明全,张彬
收稿日期:
修回日期:
出版日期:
LENG Mingquan, ZHANG Bin
Received:
Revised:
Published:
摘要: 针对反馈频率较高、影响较大的1.5MW系列风力发电机组水冷系统存在的电加热器烧坏、系统压力报警、气囊破裂及电控逻辑异常等故障进行了分析,根据分析结果提出了更新水冷系统说明书交付资料、优化设备组件及完善主控系统电控程序等建议,为水冷系统的设计优化和日常维护提供参考。
关键词: 风力发电机, 变流器, 水冷系统, 故障分析, 优化建议, 电控逻辑
Abstract: Some faults of the watercooling system occurred in 1.5MW series wind driven generator set with higher frequency feedback and great influence, such as the electric heater burning out, the system pressure alarming, the aerocyst cracking and the abnormal electric control logic and others, were analyzed. These faults were analyzed; and according to the analysis result, several suggestions, such as to update the delivered manual of the watercooling system, to optimize the equipment subassemblies, to perfect the electrical control program of the master control system and others, were put forward, which provides certain reference for design optimization and daily maintenance of the watercooling system.
Key words: wind driven generator, converter, water-cooling system, fault analysis, optimization, electrical control logic
冷明全;张彬. 风力发电机变流器水冷系统故障原因分析及优化[J]. 华电技术, 2012, 34(3): 78-81.
LENG Mingquan;ZHANG Bin. Analysis on reason of watercooling system fault of wind driven generator converter and optimization[J]. Huadian Technology, 2012, 34(3): 78-81.
/ 推荐
导出引用管理器 EndNote|Ris|BibTeX
链接本文: https://www.hdpower.net/CN/
https://www.hdpower.net/CN/Y2012/V34/I3/78