6kV电机低电压保护误动原因分析及改进

  

  1. (宁夏中宁发电有限责任公司,宁夏中宁〓755100)
  • 出版日期:2014-08-25

Analysis on reasons of false trip of 6kV motor undervoltage protection and improvement

  1. (Ningxia Zhongning Power Generation Company Limited, Zhongning 755100, China)
  • Published:2014-08-25

摘要: 摘要:针对一起由于人为误操作造成电压互感器(PT)断线未闭锁低电压保护而引发的事故,分析了保护装置PT断线的原理、判断逻辑以及外部电磁式元件对保护装置电压采集回路的影响,对低电压保护动作闭锁逻辑进行了改进和完善,以避免误动事故的发生。

关键词: 关键词:低电压继电器, 电磁干扰, PT断线闭锁, 低电压保护, 误动

Abstract: Abstract:An undervoltage protection false trip accident was analyzed. The voltage transformer wire broken fault occurred firstly due to operator's incorrect manipulation. Then the PT disconnection did not lock the undervoltage protection. So the undervoltage protection tripped incorrectly. The principle and judgement logic of the protection device PT disconnection were analyzed. The influence of outside electromagnetic elements on the voltage sample circuit of the protection device was investigated. The undervoltage protection lockout logic was improved and perfected, and the false trip accident was avoided.

Key words: Keywords:undervoltage relay, electromagnetic interference, PT wirebroken lockout, undervoltage protection, false trip