越南沿海三期电站#1机组振动分析和处理

  

  1. 中国成达工程有限公司,成都〓610041
  • 出版日期:2017-08-25 发布日期:2017-09-12

Vietnam Duyen Hai 3 Thermal Power Plant unit No.1 vibration analysis and treatment

  1. China Chengda Engineering Company Limited, Chengdu 610041, China
  • Online:2017-08-25 Published:2017-09-12

摘要:

越南沿海三期电站汽轮发电机组在空负荷和正常运行状态下的振动值偏大,尤其是在发电机温升试验时,发电机的振动值随着励磁电流的变化而变化。通过分析认为,机组的振动主要是由转子的不平衡量引起,通过现场动平衡,有效地解决了机组在各工况下振动偏大的问题。

关键词:

Abstract:

The generating unit of Vietnam Duyen Hai 3 Thermal Power Plant was overvibrating in noload and normal operating condition. Especially in generator temperaturerise test, the vibration value varied with variation of exciting value. After analysis, unit vibration was mainly caused by rotor imbalance. By site balance adjustment, the problem of overvibration was effectively solved.