Huadian Technology ›› 2008, Vol. 30 ›› Issue (2): 67-69.
• 控制技术 • Previous Articles Next Articles
HAN Ling-zhu
Received:
Revised:
Published:
Abstract: By calculating the fault current of 6kv system FC circuit in power plant, and analyzing the ampere-second characteristic of NT type high voltage fuse, while considering the current characteristics when the high voltage motor started, stopped because of blockage, and bearing blocked, the choice method of FC circuit high voltage contactor time limit current quick break protection value was supplied.
Key words: FC circuit high voltage contactor, time limit current quick break protection, configuration method
HAN Ling-zhu. Choice of FC circuit high voltage contactor time limit current quick break protection value [J]. Huadian Technology, 2008, 30(2): 67-69.
/ Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.hdpower.net/EN/
https://www.hdpower.net/EN/Y2008/V30/I2/67