Analysis of factors influencing on thermal efficiency of heater of an introduced 300MW unit

WANG Yi1,YAN Litao2   

  1. 1.Urumqi Thermal Power Plant, Huadian Xinjiang Power Generation Corporation Limited, Urumqi 830017, China; 2.The School of Energy and Power Engineering, North China Electric Power University, Baoding 071003, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2009-12-25 Published:2009-12-25

Abstract: Combining with the requirement of unit energysaving reformation, based on the theory of equivalent enthalpy drop method, the influence of temperature difference between heater terminals and steam extraction pressure loss on the thermal efficiency of the regenerative heating system of an introduced 300MW unit was analyzed quantitatively. Aiming at the result of the quantitative analysis, the defects and problems in the regenerative heating system structure were found, and the result can be used as a foundation for optimal operation of regenerative heating system of similar units.

Key words: equivalent enthalpy drop method, temperature difference between heater terminals, steam extraction pressure loss, thermal power system operation optimization