Huadian Technology ›› 2009, Vol. 31 ›› Issue (12): 48-50.
• 技术交流 • Previous Articles Next Articles
ZOU Yiyun, FENG Wei
Received:
Revised:
Published:
Abstract: In process of abnormal situation analysis of a substation in Taizhou area, it was found that when the measurement and control device D25 manufactured by certain company was matched with line protection, in which the CZX-12A operational relay box was used, if the relay in measurement and control box acted abnormally, the automatic recloser of the line protection should be latched. In this situation, if a single phase earthing fault occurred, the switch should trip single phase, and the recloser should not recluse, so the single earthing fault may translate into multiphases short circuit fault, and the equipment damage in fault point may be enhanced. This is a hidden danger for safety operation of power grid. The abovementioned phenomenon was analyzed, and relevant improvement scheme was proposed.
Key words: measurement and control device, automatic recloser, single phase earthing fault
ZOU Yiyun;FENG Wei. Influence of matching of measurement and control device D25 with CZX-12A on recloser of 220kV line[J]. Huadian Technology, 2009, 31(12): 48-50.