The causes analysis on overtemperature of main steam of supercritical oncethrough boiler at initial stage of startup

MA Shidong   

  1. Anhui Huadian Suzhou Power Generation Corporation Limited, Suzhou 234101, China
  • Received:1900-01-01 Revised:1900-01-01 Published:2009-04-25

Abstract: At the startup process during commissioning period of No.1 600MW supercritical units in Anhui Huadian Suzhou Power Generation Corporation Limited, the problem of little overtemperature of the main steam occurred many times, especially in the first time of parallel in power grid. The main reasons were the small burning heat load, too much air flow and fuel, larger feedwater flow, unreasonable designs of attemperating water. In these regard, the series of measures were adopted, such as lowering the feedwater quantity during ignition, reducing fuel input, improving combustion, increasing combustion heat load, controlling the negative pressure of furnace at -100Pa, the total air flow of 0.5 ~ 0.6 million m3/h, and raising feedwater temperature above 100℃,etc. the problem of overtemperature of main steam during initial stage of startup process has been solved, and all the parameters have reached designed demands.

Key words: supercritical unit, once-through boiler, start up commissioning, steam temperature change, adjustment measure