Analysis on the flow resistance characteristics of direct air cooled condenser at the air side

ZHANG Wei1, LIU Haifeng2, SHI Lei3   

  1. 1.School of Environmental and Municipal Engineering, North China Institute of Water Conservancy and Hydroelectric Power, Zhengzhou 450011,China;2.China Huadian Engineering Corporation Limited, Beijing 100048, China;3. School of Civil Engineering, Beijing Jiaotong University, Beijing 100044, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2009-04-25 Published:2009-04-25

Abstract: In the direct air cooling system, the key technology of air supply system is the optimal selection and design of axial fan. It is of great importance on the optimal design and economical operation of air cooling system. The static pressure of the axial fan depends on the flow resistance of the air cooled condenser (ACC).The causes of pressure losses when air passing through each part of A-shape air cooled condenser were analyzed. The resistance coefficient at different part of the bundles was determined. It offers good help for the optimal design of direct air cooling system.

Key words: engineering thermophysics, direct air cooling, single row tube, resistance coefficient, static pressure