Huadian Technology ›› 2009, Vol. 31 ›› Issue (8): 19-21.
• 研究与开发 • Previous Articles Next Articles
YANG Shiyong
Received:
Revised:
Published:
Abstract: The Aphase grounding fault of 110kV Qiahe No.1 line in Qiafuqihai Hydropower Station of Xinjiang Ili River Basin Development and Construction Administrative Bureau was occurred. After that, the line protection acted correctly, but Aphase breaker rejected to trip, the local backup protection (bus) rejected to act, and remote backup protection acted and caused accident scope expansion. The accident field operators considered the problems unilaterally, and this leaded trial power transmission to be failure and the accident scope to expand once again. The reason of the accident was analyzed. According to the concrete condition after protection action, and according to the protection and fault record message, a scientific decision was got, and the accident expansion was avoided.
Key words: breaker refusal of tripping, protection refusal of tripping, line grounding fault, reason analysis, countermeasure, measure
YANG Shiyong. Reason analysis of beaker refusal of action and relevant countermeasure[J]. Huadian Technology, 2009, 31(8): 19-21.
/ Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.hdpower.net/EN/
https://www.hdpower.net/EN/Y2009/V31/I8/19
Research on gas turbine combustion pressure fluctuation and the key technologies for its measurement
Experimental study of dissolved oxygen’s effect on dissolved hydrogen analyzer of the main steam
Reasons analysis for tube blasting and preventive measures for superheater of 1000MW supercritical boiler
Research on automatic and seamless switching technology for virtual backup measurement and control units in smart substations