Huadian Technology ›› 2010, Vol. 32 ›› Issue (6): 70-71.
• 技术交流 • Previous Articles Next Articles
LIU Fang
Received:
Revised:
Published:
Abstract: A fault of Guangdong Zhuhai Jinwan Power Generation Corporation Limited, which caused the stator earthfault protection acted, was analyzed, and the analysis proved that the protection acted correctly and timely. Starting from the questionable point that the fault phenomenon was not accordance with the actual inspection, by using the vector diagram, according to the intuitive analysis, the fault process was determined that the opencircuit fault was occurred first, and then the shortcircuit fault occurred. By further analysis, the conclusion obtained that the protection action process was fully accordance with the field inspection result, and it is verified that the settings of stator earthfault protection is correct.
Key words: stator earth-fault protection, zero-sequence fundamental harmonic, third harmonic
LIU Fang. Analysis on a fault which caused the stator earthfault protection action[J]. Huadian Technology, 2010, 32(6): 70-71.