Huadian Technology ›› 2011, Vol. 33 ›› Issue (11): 23-27.
• 技术交流 • Previous Articles Next Articles
ZENG Aiping
Received:
Revised:
Published:
Abstract: In the Hunan Changsha Power Generation Corporation Limited, after the overhaul of the unit No.1, the mediumpressure regulating valve suddenly opened during rolling the turbine and warming up two times, and the rotate speed was increasing quickly and can not be controlled. The digital electrohydraulic control system and the reason of the mediumpressure regulating valve suddenly opening were analyzed in detail. After the effective measures were adopted, the suddenly opening of the mediumpressure regulating valve was not occurred again.
Key words: digital electro-hydraulic control system (DEH), warming up logic, speed increasing, reason analysis
ZENG Aiping. Reason analysis of suddenly opening of mediumpressure regulating valve in digital electrohydraulic control system[J]. Huadian Technology, 2011, 33(11): 23-27.