Huadian Technology ›› 2011, Vol. 33 ›› Issue (2): 30-32.
• 技术交流 • Previous Articles Next Articles
ZHAO Yuzhu,WANG Zhangsheng,XU Houda
Received:
Revised:
Online:
Published:
Abstract: The particular case of the micro electro hydraulic control system (MEH) reformation of the boiler feed pump turbine and the fault of difficulty in latchon occurred in operation after the reformation were introduced. According to the experimental analysis, the reasons of the MEH system fault were found out, and the optimizing measures were given, the problems in MEH reformation were solved.
Key words: boiler feed pump turbine (BFPT), speed control system, magnetic valve, throttle orifice plate, latch-on
ZHAO Yuzhu;WANG Zhangsheng;XU Houda. Reformation and optimized operation of speed control system of boiler feed pump turbine[J]. Huadian Technology, 2011, 33(2): 30-32.