Huadian Technology ›› 2011, Vol. 33 ›› Issue (2): 37-37.
• 技术交流 • Previous Articles Next Articles
ZHANG Xiaobing
Received:
Revised:
Published:
Abstract: The reasons of a unit tripout accident caused by abnormal melt of the fuse in PT primary side in the generator outlet were analyzed. The defections in the selection of PT primary fuse and in the voltage sampling mode of the protection device were pointed out; the improvement and preventive measures were put forward.
Key words: ground protection, primary fuse, fuse melt, potential transformer (PT) of generator
ZHANG Xiaobing. Analysis and treatment on a unit tripout accident caused by tripping of generator ground protection[J]. Huadian Technology, 2011, 33(2): 37-37.