Huadian Technology ›› 2011, Vol. 33 ›› Issue (4): 49-51.

• 技术交流 • Previous Articles     Next Articles

Analysis on problems existed in emergency governor of 330 MW unit and countermeasures

WEI Xiaobao1,SHAN Hongliang2   

  1. 1.State Nuclear Power Engineering Corporation Limited, Shanghai 200233, China; 2.Henan Second Thermal Power Construction Company, Zhengzhou 450051, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2011-04-25 Published:2011-04-25

Abstract: In debugging of the 330 MW unit of a power plant, it was found that the stay hook of the emergency governor can not reset sometimes. According to analysis, the reason of the defect mentioned above is that the moment of torsion of parallelarranged doublesupported springs installed in location near the stay hook is insufficient. The moment of torsion of the springs was increased by some means, and the problem of stay hook reset was solved.

Key words: emergency governor, reset, parallel-arranged double-support springs, moment of torsion, torsional deformation angle