Huadian Technology ›› 2011, Vol. 33 ›› Issue (7): 59-60.
• 技术交流 • Previous Articles Next Articles
SHU Yishi, WANG Wei, YU Peijie
Received:
Revised:
Published:
Abstract: The configuration of the PST1200 series digital transformer protection device was introduced. In a 220kV substation, an accident of main transformer highvoltage side bushing downlead clamp fracture was happened in its copperaluminum transitional zone. The corresponding action logic of the protection device was analyzed; and it was pointed out that when the circuitfracture accident happened, the protection device should not activate or act to trip because of that the device can not feel the fault current. Aiming at common fracture accidents, some improvement measures were put forward, which is helpful for decreasing accident.
Key words: transformer protection, bushing downlead, clamp, fracture
SHU Yishi;WANG Wei;YU Peijie. Analysis on a fracture accident of transformer bushing downlead clamp[J]. Huadian Technology, 2011, 33(7): 59-60.