Huadian Technology ›› 2011, Vol. 33 ›› Issue (8): 27-29.
• 技术交流 • Previous Articles Next Articles
WANG Dongya,LIN Shaoming
Received:
Revised:
Online:
Published:
Abstract: In the Guangdong Zhuhai Jinwan Power Generation Company Limited, during the test of the generatortransformer unit protection device G60, it was found that the protection 'all stopping when 500kV switch tripped' configured in the protection device acted incorrectly. Based on indepth analysis, it was considered that the main reason of the fault is the malfunction of the generatortransformer unit protection device. The improvement method of the protection logic was put forward; the protection malfunction happening again was avoided, and a serious hidden danger of the generatortransformer unit protection device was eliminated.
Key words: generator-transformer unit, malfunction of protection, G60 device, reason analysis, improvement of protective logic
WANG Dongya;LIN Shaoming. Analysis and improvement of malfunction of protection 'all stopping when 500kV switch tripped' under 3/2 connection mode[J]. Huadian Technology, 2011, 33(8): 27-29.