Huadian Technology ›› 2012, Vol. 34 ›› Issue (5): 60-62.
• 技术交流 • Previous Articles Next Articles
MAO Yisheng
Received:
Revised:
Published:
Abstract:
In the desulphurization control system of units No.3 and No.4 in Guangdong Zhuhai Jinwan Power Generation Company Limited, the Foxboro I/A Series
distributed control system is adopted. The off-line and restarting phenomenon of single or double controllers in system occurred randomly, which threatens
the safe and stable operation of the unit severely. The synchronous records of the system management counter and the controller were analyzed to determine
the network problem; the node bus network had been monitored, and the data streams between stations were analyzed. It was determined finally that the data
acquisition and send program of the supervisory information system in plant level, Opifox, caused the congestion of the node bus network of desulphurization
distributed control system, which makes the two controllers to be asynchronous and to start up again. The data acquisition and send program had been
replaced, and at last, the difficult problem was solved.
Key words: distributed control system (DCS), controller restarting, supervisory information system (SIS) in plant level, Opifox, node bus
MAO Yisheng. Reason analysis and treatment of restarting fault of I/A Series two controllers[J]. Huadian Technology, 2012, 34(5): 60-62.