Abstract: In the switch over process of the service power supply in unit No.11of the Panzhihua Branch of Huadian Sichuan Power Generation Company Limited ,the voltage of 400V I B segment was failed, the butterfly valve of the operation vacuum pump B could not linked, and the standby vacuum pump A could not linked startup, which caused the lower vacuum tripping of the unit. The reasons of the faults were analyzed, and it was determined that the main reason of the unit lower vacuum tripping is irrational design of the control loop of vacuum pump. A series of technical improvement measures were adopted, and the operation reliability and safety of the unit were increased effectively.
Key words: vacuum, vacuum pump, control loop, technical reformation
WEI Shengluan. Reason analysis and treatment of unit lower vacuum trip caused by vacuum pump refusing to linked act[J]. Huadian Technology, 2012, 34(6): 58-59.