Huadian Technology ›› 2012, Vol. 34 ›› Issue (8): 44-46.
• 技术交流 • Previous Articles Next Articles
YIN Song
Received:
Revised:
Published:
Abstract:
After the 700MW unit of a power plant had been connected into grid, the auxiliary power switchover had failed; due to the bus voltage loss, the 1A
stator cooling water pump was stopped; although the 1B stator cooling water pump started automatically, but the stator cooling water pressure difference low
signal had been given out, and protection device had tripped and caused the generator disconnection from the power system. The reason of the protection trip
was analyzed in depth; and the hidden dangers were found. Some prevent measures were proposed with 3 aspects of measures such as optimizing the interlock
protection logic, replacing the instruments by new type instruments and formulating antiaccident measures; and the safety hidden dangers for unit operation
were eliminated effectively.
Key words: stator cooling water, disconnection, interlock control, auxiliary power
YIN Song. Analysis on unit disconnection accident of 700MW unit caused by switchover failure of auxiliary power and preventive measures[J]. Huadian Technology, 2012, 34(8): 44-46.