Analysis on reason causing the 500kV main transformer breaker failure protection to refuse to trip

WANG Tianmin, ZHANG Xiaogang, GAO Bo   

  1. Anyang Power Supply Company, Anyang 455000, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2012-09-25 Published:2012-09-25

Abstract: It was found that after the 500kV main transformer breaker failure protection acted, the function of intertrip of the switches in three sides of the main transformer can not be realized in the transmission debug process of a 500kV substation. The fault in this circuit was analyzed, and it was pointed out that the main reason of this fault is the design error which result the malfunction of the 500kV main transformer breaker failure protection to refuse to trip . A solution was proposed to avoid effectively refusing to trip and tripping improperly.

Key words: substation, main transformer, circuit breaker failure, refuse to trip, improper tripping