Huadian Technology ›› 2012, Vol. 34 ›› Issue (S1): 50-51.
• 技术交流 • Previous Articles Next Articles
WU Zhenghua, WANG Dongjue
Received:
Revised:
Published:
Abstract: The current transformer for the smallcapacity transformer in a 220kV system was configured improperly. When the fault occurred, the current transformer saturated seriously, which led the protection refused to trip or tripped incorrectly and caused the fault enlargement. In order to ensure the reliability of the protection, the current transformer and the protection configuration must be improved. Aiming at the difficulties in the improvement, the improvement scheme of the current transformer and the improvement scheme of the protection configuration were proposed. The implementation of the improvement schemes can increase the reliability of the protection greatly.
Key words: current transformer, protection configuration, saturation, refuse to trip, transformation ratio, accuracy class, improvement scheme
WU Zhenghua;WANG Dongjue. Analysis on improvement scheme of configuration of current transformer and protection for smallcapacity transformer in 220kV system[J]. Huadian Technology, 2012, 34(S1): 50-51.