Huadian Technology ›› 2012, Vol. 34 ›› Issue (S1): 58-59.
• 技术交流 • Previous Articles Next Articles
WU Zhenghua
Received:
Revised:
Published:
Abstract: In a power generation company, the dedicated fault recorder was not configured for the smallcapacity generatortransformer set, and this does not accord with the rule of the file DL/T 553—1994, ‘The technical criteria for transient fault recording in 220~500kV power system’. Therefore, several improvement plans were put forward. Various improvement plans were analyzed and compared with each other from many aspects, such as the analog variable connected into the fault recorder, the installation sites, the number of the fault recorders, the access positions of the analog variables and the length of the secondary cable. The best improvement plan was recommended and implemented.
Key words: generator-transformer set, fault recorder, installation site, secondary cable, improvement plan
WU Zhenghua. Analysis on configuration scheme of fault recorder for smallcapacity generatortransformer set[J]. Huadian Technology, 2012, 34(S1): 58-59.