Analysis on operation control mode of condensate pump of 1 000 MW unit

XING Lijun, MA Yongsheng   

  1. (Huadian Laizhou Power Generation Company Limited, Laizhou 261400, China)
  • Received:1900-01-01 Revised:1900-01-01 Online:2013-03-25 Published:2013-03-25

Abstract: In normal operation of the 1000MW unit, the operation mode of the condensate pumps is that two pumps are put into operation, and one pump is standby. The two operating pumps are controlled by variable frequency control technology, and the standby pump is driven by 50Hz power source. Along with increase of the unit peak shaving depth, the variation range of the unit load also increases. After the condensate pump was controlled by variable frequency control technology, it is very important to keep the condensate pump outlet mainpipeline pressure and the water level of the deaerator to be stable in normal operation. A solution of the operation and control mode of the condensate pump of 1000MW unit was proposed.

Key words: condensate pump, variable frequency, deaerator, main-pipeline pressure