Abstract: During running period of a 600MW supercritical unit, the temperature of output water of the HP heater was much higher than the designed value. The problem was analyzed from the operation system and the measuring circuit, and it was found that the reason of the higher temperature was that the temperature sensing element is not matched with the compensating wire in the measuring circuit, and the measured temperature value was incorrect. The temperature sensing element had been replaced, and the measured temperature became correct.
Key words: 600MW supercritical unit, high-pressure heater (HP heater), output water temperature, higher, measuring circuit
PENG Bowei. Analysis on reason of higher output water temperature of HP heater in 600MW unit and countermeasures[J]. Huadian Technology, 2013, 35(4): 5-7.