Analysis on reasons of higher turbidity of circulating water and countermeasures

YAN Jianwei, DONG Chaozeng   

  1. (Datang Linzhou Thermal Power Company Limited, Linzhou 456500, China)
  • Received:1900-01-01 Revised:1900-01-01 Online:2013-05-25 Published:2013-05-25

Abstract: The turbidity of the circulating water of unit NO.1 of Datang Linzhou Thermal Power Company Limited increased abnormally. According to analysis, it was determined that the reasons of higher turbidity of circulating water are as below: the cleaning period for the bottom of circulating water cooling tower is too long, the ambient environment of the cooling tower is bad, the bactericide peeled off and polluted by paste, the circulating water pump causes the paste to roll up during starting and stopping, and so on. The countermeasures and suggestions for controlling the turbidity of the circulating water were put forward.

Key words: water cooling tower, circulating water, turbidity, bactericide, circulating water pump