Huadian Technology ›› 2013, Vol. 35 ›› Issue (7): 53-55.
Previous Articles Next Articles
Published:
Abstract:
Abstract:The function of transformer balance winding was introduced. An infrequent short circuit fault of transformer balance winding was introduced. The transformer is installed in an aircooled power plant and connected in mode of Yyn0+d, and the short circuit fault of its balance winding had caused the differential protection to trip. A new fast method was adopted for transformation and calculation of first and second currents of the transformer. The fault position can be determined correctly by the new method, which provides a base for the fault treatment.
Key words: Key words:transformer, balance winding, differential protection, simplified analysis on short circuit fault
LI Zecai, CHENG Zhongyue, LI Xirong, PAN Lehong, YUAN Lancheng. Analysis on transformer balance winding fault of an aircooled power plant and treatment[J]. Huadian Technology, 2013, 35(7): 53-55.