Analysis on transformer balance winding fault of an aircooled power plant and treatment

  

  1. (Huaneng Tongchuan Power Plant, Tongchuan 727100, China)
  • Online:2013-07-25 Published:2013-08-20

Abstract:

Abstract:The function of transformer balance winding was introduced. An infrequent short circuit fault of transformer balance winding was introduced. The transformer is installed in an aircooled power plant and connected in mode of Yyn0+d, and the short circuit fault of its balance winding had caused the differential protection to trip. A new fast method was adopted for transformation and calculation of first and second currents of the transformer. The fault position can be determined correctly by the new method, which provides a base for the fault treatment.

Key words: Key words:transformer, balance winding, differential protection, simplified analysis on short circuit fault