Abstract: Abstract:The source injection type stator grounded fault protection in the protection cabinet A, B of Generator No.5 in Goupitan Hydropower Plant tripped, and this caused active load of the plant 527.6MW to be shed. The Bphase outlet potential transformer of the generator No.5 had been disassembled and tested, and it was found out that the main reason of load shedding of the 600MW generator is the damage of the potential transformer. The relevant countermeasures were proposed, which laid a solid foundation for the fault treatment.
Key words: Key words:source injection type stator grounded fault protection, potential transformer, turntoturn short circuit, reason analysis;measure