Huadian Technology ›› 2013, Vol. 35 ›› Issue (9): 39-40.
Previous Articles Next Articles
Published:
Abstract: Abstract:The incorrect tripping problem of REG670 rotator grounding protection of 600MW unit in Huadian International Zouxian Power Plant was analyzed. It was excluded that the incorrect tripping may be caused by harmonic, and the actual reason of incorrect tripping was found, which is that the rated value of the analog current channel of REG670 for rotator grounding protection is selected to be 5A. The solving methods of the incorrect tripping of REG670 rotator grounding protection were proposed.
Key words: Key words:rotator, grounding protection, incorrect tripping, solving method
SUN Jing. Analysis on reasons of incorrect tripping of 600 MW unit REG670 rotator grounding protection[J]. Huadian Technology, 2013, 35(9): 39-40.