Huadian Technology ›› 2014, Vol. 36 ›› Issue (10): 40-42.

Previous Articles     Next Articles

Analysis on reason of tripping accident of generator stator grounding protection

  

  1. (Sichuan Guang’an Power Generation Company Limited, Guang’an 638000, China)
  • Online:2014-10-25 Published:2014-11-20

Abstract: Abstract:The operation situation of the 600MW coalfired turbogenerator set and its generatortransformer set protection in a power plant was introduced. Based on inspection and test, it was found that there was stagnant water in the rubber sleeve in lowvoltage side of the main transformer, and which caused the generator stator grounding protection tripping accident. The concrete reformation and preventive measures were proposed.

Key words: Keywords:generator, stator grounding, protection tripping, rubber sleeve, preventive measure