Huadian Technology ›› 2014, Vol. 36 ›› Issue (10): 40-42.
Previous Articles Next Articles
Published:
Abstract: Abstract:The operation situation of the 600MW coalfired turbogenerator set and its generatortransformer set protection in a power plant was introduced. Based on inspection and test, it was found that there was stagnant water in the rubber sleeve in lowvoltage side of the main transformer, and which caused the generator stator grounding protection tripping accident. The concrete reformation and preventive measures were proposed.
Key words: Keywords:generator, stator grounding, protection tripping, rubber sleeve, preventive measure
ZHANG Tailin. Analysis on reason of tripping accident of generator stator grounding protection[J]. Huadian Technology, 2014, 36(10): 40-42.