Huadian Technology ›› 2014, Vol. 36 ›› Issue (3): 46-48.
Previous Articles Next Articles
Published:
Abstract: Abstract:After adding reclaimed water to doublepass condenser, the risk of scale formation in the tube of condenser has increased. According to calculation and analysis, this article brings out the method of adding middle water temperature measuring point in the returning water chamber of doublepass condenser. This method helps find out the reason why the heat transfer of condenser is poor and the degree of supercoiling is high, which can monitor the scale formation and air leakin in air leakin effectively.
Key words: Keywords:doublepass condenser, reclaimed water, scale formation, water temperature measuring point
WU Xin 1,ZHU Deming 1,WU Ning 2. Practice of adding water temperature middle measuring point in doublepass condenser[J]. Huadian Technology, 2014, 36(3): 46-48.