Abstract: Abstract:Aiming at the false trip accident of the 10kV line protection in an 110kV intelligent substation, the protection devices and the secondary circuit were inspected, and the site record files were analyzed. It was determined that the reason of the false trip accident is abnormity of the AC current sampling of the protection, and the reason of the abnormal AC current sampling is looseness of the AC plugin components, which causes floating voltage in circuit. At last, the relevant preventive measures were proposed.
Key words: Keywords:intelligent substation, line protection, false trip, AC current sampling, plugin component, floating voltage
LIANG Yongxin, WU Dongdong, SONG Yufeng, MA Yongzhan. Analysis on a false trip accident of 10kV line protection[J]. Huadian Technology, 2014, 36(7): 39-41.
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.hdpower.net/EN/
https://www.hdpower.net/EN/Y2014/V36/I7/39
一起电子互感器异常引发的复杂发展性故障分析及改进