Huadian Technology ›› 2015, Vol. 37 ›› Issue (11): 52-53.
Previous Articles Next Articles
Published:
Abstract:
Abstract:Since the pH value,electrical conductivity and copper content of stator cooling water in plant generator are abnormal,correspondent actions are taken;while,the initial effect is not obvious.After the shutdown and complete flushing of stator cooling water system,the problem is that the expander weld of stator cooling water anti siphon pipe is cracking as a result of large generator vibration.The problem is sorted out through re-welding.
Key words: ">Keywords:">stator cooling water, excess copper content, ion exchange resin, anti ">siphon pipe
ZHANG Xuehai. Abnormal cause analysis and control of stator cooling water in 600 MW unit generator[J]. Huadian Technology, 2015, 37(11): 52-53.