Causes analysis of large terminal temperature difference of 600MW subcritical generator 

  

  1. (Huadian Baiyinhua Jinshan Power Company Limited , Xilingol 026200,China)
  • Online:2015-04-25 Published:2015-06-02

Abstract: Abstract:In Huadian Baiyinhua Jinshan Power Company Limited, #1, #2 turbines′ high and low pressure heaters′ terminal temperature differences are sharply higher than the designed value, with a maximum deviation of 13.94℃. After analyzing parameters collected from 300 ,400 and 565MW, causes are concluded that both the heaters′ water level and the extraction steam temperature exceeded standard values; and measures are put forward.

Key words: Keywords:heater, thermal measurement, water level, extraction steam temperature