Huadian Technology ›› 2015, Vol. 37 ›› Issue (9): 51-52.

Previous Articles     Next Articles

Calculation for short circuit current of 380V low voltage fourcore power cable

  

  1. Hubei Huadian Xiangyang Power Company Limited, Xiangyang 441141, China
  • Online:2015-09-25 Published:2015-11-26

Abstract:

Abstract:Due to most 380 V plant power system power center (PC) and motor control center (MCC) are TN-S grounding,the standard short circuit current curve in existing design handbook cannot satisfy the practical demand.This paper provided methods to calculate the short circuit current of 380 V four core power cable from PC to MCC of plant power system.Based on these methods,the relationship between short circuit current and cable length was indicated,which can be applied for relay protection value setting and sensitivity verification.

Key words: ">Keywords:380">V plant power system">;">four">core power cable">;">short circuit current