Huadian Technology ›› 2016, Vol. 38 ›› Issue (10): 40-43.

Previous Articles     Next Articles

Treatment to increase 1050MW unit steam water SiO2 mass concentration test analysis accuracy

  

  1. Huadian Laizhou Power Plant Company Limited, Yantai 261400, China
  • Online:2016-10-25 Published:2016-11-23

Abstract:

Abstract:Ultrasupercritical requires high quality water vapor.SiO2 contains is very low. The tolerance of existing spectrophotometry method to measure SiO2 content is very big. So that, it is difficult to monitor the varying of SiO2 content. Take a 1050MW ultracritical onethrough unit as example, this paper examined the tolerance causes from drug, method, environment and instrument. Test operation and procedure was improved. SiO2 mass concentration accuracy was significantly increased.

Key words: