W boiler Y type heavy oil gun blockage cause analysis and treatment

  

  1. 1.China Datang Corporation Science and Technology Research Institute Central China Branch, Zhengzhou 450000, China; 2.Xi’an Thermal Power Research Institute Company Limited, Xi’an 710032, China
  • Published:2017-01-25

Abstract:

While W boiler Y type oil gun burning heavy oil, carbon deposition, coking, nozzle and oil pipe blockage usually happened. Based on the incident of continuous extinguishment, poor atomization and continuous decreased oil flow that happened during a newly built boiler commissioning, the blockage cause was analyzed. Treatment and improvement measurements was taken accordingly. After treatment, the oil gun blockage was significantly improved, and work fine during boiler start. The problem of oil gun cleaning was fundamentally solved. Oil gun long term and continuous operation was ensured.