220kV transformer slight gas protection reaction analysis and treatment

  

  1. Jiangsu Huadian Qishuyan Power Generation Company Limited, Changzhou 213011,China
  • Online:2017-03-25 Published:2017-04-26

Abstract:

As the primary protection for oil immersed transformer, gas protection reflected the kind of inside failure. Normally, slight gas reaction to warn, and heavy gas protection to trip. By analysing a slight gas reaction of a 220kV transformer, a false warn caused by moisture absorber blockage was found. This could be referred for oil immersed transformer maintenance.