Reason analysis of 380V switch override in desulfurization system and its treatments

  

  1. Yunnan Huadian Kunming Power Generation Company Limited, Anning 650308, China
  • Online:2017-03-25 Published:2017-04-26

Abstract:

The incident that a power plant’s 380V desulfurization system busbar incoming switch override tripped multiple times was analysed. The main cause was determined that the load was improperly distributed and improper protection value setting. After redistributed the critical load and adjusted the setting valued, the stability of desulfurization system was increased.