EMTPbased interconnection cable lightning overvoltage affecting factors analysis

  

  1. 1.State Grid Corporation of China Direct Current Construction Company,Beijing 100032,China;2.State Grid Electric Power Research Institute Wuhan NARI Company Limited,Wuhan 430074,China;3.Ningxia Power Transmission and Distribution Construction Company,Yinchuan 750000,China
  • Published:2017-07-25

Abstract:

Based on electromagnetic transient program(EMTP) simulation model, lightning current waveform,cable alignment,cable length,impulse grounding resistance,and the relationship of cable end load and cable lightning overvoltage was studied. The result indicated that steeper the wave front is,greater the overvoltage is. The lightning overvoltage is relatively small if cable is horizontally aligned. Lightning overvoltage is maximum if the cable length is 3000m. Cable aligned in same length will reduce lightning overvoltage. Impulse grounding resistant and soil resistant can barely affect the lightning overvoltage. Bigger the load is,greater the cable lightning overvoltage is. The cable lightning overvoltage is greater if load is capacitive or inductive.