  1. 1.Guodian Nanjing Automation Company Limited, Nanjing 210003, China; 2.Nanjing Guodian Nanzi Automation Company Limited, Nanjing 211153, China
  • Online:2017-09-25 Published:2017-10-10

Abstract:

Utilizing installed series capacitor double circuits on the same tower grounding failure zero sequence network, the influence of the zerosequence power direction element and zero sequence differential protection on the two sides protection installation is analyzed in the case of high resistance failure at the outlet of the string and the failure of the MOV. Analysis indicated that series compensation capacitor may lead to far away from the side of series compensation protection of zero sequence power direction relay from action, as a protection of high resistance earth fault zerosequence differential protection sensitivity and the lower even refused to move. The simulation test verifies the correctness of the theoretical analysis and puts forward the principle of the main protection.