Fault analysis and calculation of voltage transformerinterturn short circuit at generator outlet

  

  1. Datang CentralChina Electric Power Test Research Institute, Zhengzhou 450001, China
  • Published:2018-11-26

Abstract:

Taking a stator grounding fault protection caused by interturn short circuit of voltage transformer as an example, the interturn short circuit of voltage transformer primary winding is determined to be the cause of the protection action through comprehensive analysis of fault waveform and test data. The analysis and calculation on equivalent circuit of terminal voltage imbalance caused by the equivalent impedance reduction as the voltage transformer interturn circuit is shorted are made, which is helpful to understand the process of interturn short circuit. Finally, several possible situations and preventive measures leading to interturn short circuit are discussed, which can provide reference for the monitoring and safe operation of voltage transformer.