Inspection and treatment of a multipoint ground fault of an excitation transformer core

  

  1. Jiangsu Huadian Qishuyan Power Generation Company Limited, Changzhou 213011, China
  • Online:2018-12-25 Published:2019-01-28

Abstract:

Failure of the relevant components of excitation transformer (core body, clamps, pull plates, grounding devices, etc.) will affect the safe operation of the transformer. The multipoint grounding of the iron core will create a closed loop between the grounding points. There is magnetic flux and induced potential at the linking parts, which can form a circulating current and lead to local overheating. The rise of the local core temperature of the transformer will accelerate the insulation aging and even cause the hightemperature trip protection. Therefore, the multipoint grounding of the iron core is extremely harmful to the transformer.It must be taken seriously and eliminated. Taking the multipoint grounding of a gas turbine excitation transformer core as an example, the method is analyzed, and some suggestions are provided for the maintenance and repair of related faults.