Huadian Technology ›› 2018, Vol. 40 ›› Issue (6): 26-27.

Previous Articles     Next Articles

The maloperation of common variable ratio differential protection caused by the main transformer zero sequence CT disconnection

  

  1. Huaneng Tongchuan Zhaojin Power Plant, Tongchuan 727100, China
  • Online:2018-06-25 Published:2018-08-21

Abstract:

It analyzes an accident due to the disconnected point of zerosequence CT circuit of a main transformer on the power plant side. When a singlephase ground fault occurs outside the grid side zone, it leads to a utility variable ratio differential protection. It reveals that if there is disconnected point in a zerosequence CT secondary side, the induced secondary high voltage may affect the adjacent AC sampling loop. Analyzing the typical wave characters of this accident, specific preventive measures are put forward as references for the unknown accident.