Ground point principle and case analysis of current transformer

  

  1. Inner Mongolia Datang International Togtoh Power Generation Company Limited,Togtoh 010216,China
  • Online:2018-08-25 Published:2018-09-20

Abstract:

Measured circuits shunts caused by twopoint grounding of the current transformer secondary winding, leaded to malfunction of main transformer differential protection. Aiming at the accident, analysis on possible current transformer false wiring was made at the scene. It expounds the importance and necessity that only onepoint ground of current transformer secondary circuit is the allowed in the protection cabinet screen.