Huadian Technology ›› 2018, Vol. 40 ›› Issue (9): 15-17.

Previous Articles     Next Articles

Neutral test on the utilization of ceramic UF in circulating cooling wastewater in coalfired power plant

  

  1. 1.Huadian Tengzhou Xinyuan Thermal Power Company limited, Zaozhuang 277500, China;2.Nanostone Water Technology(Shanghai) Company limited, Shanghai 200041,China
  • Online:2018-09-25 Published:2018-10-12

Abstract:

Circulating cooling wastewater is one of the main sources of industrial wastewater of coalfired power plant. Its recycling process and equipment have been popular in wastewater zero discharge study in recent years.Taking the circulating cooling wastewater of Huadian Tengzhou Xinyuan Thermal Power Company Limited, neutral test is carried out with softened clarifiers and ceramic ultrafiltration equipment under specific operating parameters and conditions.The accumulated data prove that cooling wastewater softened and clarified by equipment with ceramic UF membrane, can keep its flux at 260L/(m2·h)stably.The chemical maintenance cleaning cycle is 12 hours.The turbidity of permeate should be less than 0.2 NTU and SDI should be less than 3.The effluent completely meet the requirements of reverse osmosis.The ceramic UF system can work well with high operating flux,operational stability and good water quality.

Key words: