Huadian Technology ›› 2019, Vol. 41 ›› Issue (8): 70-73.

Previous Articles     Next Articles

Optimization of deep frequency conversion transformation for condensate pump in 1000MW secondary reheat unit

  

  1. China Energy Group Taizhou Power Generation Company Limited,Taizhou 225327, China

  • Online:2019-08-26 Published:2019-09-06

Abstract:

In order to fully exploit the energysaving potential in a condensate pump during frequency conversion operation of a 1000MW secondary reheating unit,it is pointed out that the main factor restricting the deep frequency conversion of condensate pump is the low sealing water pressure of team turbinedriven feedwater pump.By adding sealing water boost pumps the turbinedriven feedwater pumthe operation logic can be optimized.After the deep frequency conversion transformation for condensate pump,the opening degree of the deaerator water regulating valve further increases,throttling loss decreases,the current and rotation speed of condensate pump drops.Energy is saved effectively.

Key words:

font-size: 10.5pt, mso-spacerun: 'yes', mso-font-kerning: 1.0000pt">secondary reheat unit;condensate pump;deep frequency conversion;sealing water booster pump