华电技术 ›› 2010, Vol. 32 ›› Issue (10): 46-47.

• 技术交流 • 上一篇    下一篇

一起220kV变电站主变压器跳闸事故分析

张芬   

  1. 湖北孝感市供电公司调度通信所,湖北孝感432100
  • 收稿日期:1900-01-01 修回日期:1900-01-01 出版日期:2010-10-25 发布日期:2010-10-25

Analysis on tripping of main transformer in 220kV substation

ZHANG Fen   

  1. Dispatcher Communication Office of Hubei Xiaogan Power Supply Company, Xiaogan 432100, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2010-10-25 Published:2010-10-25

摘要: 介绍了220kV变电站主变压器低压侧一组电容发生了一起短路故障的情况,短路产生的大量导电烟尘窜入临近主变压器低压侧开关柜内,烧毁主变压器低压侧CT差动电流回路电缆,造成主变压器差动保护动作。分析了整个事故动作的原因,提出了防范措施,有效地提高了主变压器供电的可靠性。

关键词: 电力系统, 故障录波, 短路, 保护动作, 防范措施

Abstract: In a 220kV substation, a short circuit fault of a capacitor set in low voltage side of the main transformer was occurred. Great amount of conductive smoke dust, which was produced by the short circuit fault, whisked into the switch cabinet near the main transformer low voltage side, and the cable of the CT difference current circuit in main transformer low voltage side was burned away, and the differential protection of the main transformer was tripped. The reasons of the whole accident were analyzed, the preventive measures were put forward, and the power supply reliability of the main transformer was raised effectively. 

Key words: power system, fault record, short circuit, protection trip, preventive measure